MicroNet SP9121 Manual Pagina 72

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 184
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 71
8 Connecting to the LonWorks Network TAC Xenta Server – Gateway, Technical Manual
72 (184) Schneider Electric Buildings AB, June 2011
04-00124-06-en
5 If required, rearrange the shortcuts.
6 Generate the project and send it to the Xenta 913.
7 Open the Communications values page in a web browser and ver-
ify that all values appear as expected.
8 Open the RTU4 values page in a web browser and verify that all
values appear as expected.
Of course you must also verify that the values appear in the RTU4
device, for example using Vista Workstation, to ensure that the commu-
nication functions as expected all the way from the energy meter,
through the Xenta 913, to RTU4.
Vista de pagina 71
1 2 ... 67 68 69 70 71 72 73 74 75 76 77 ... 183 184

Comentarios a estos manuales

Sin comentarios